PID Control, 1/16 DIN, 4 digit single display, Relay & SSR Output, 1 Alarm Output, K/J/L/RTD Input, 100-240 VAC

$103.00

Model Number:
TC4S-14R
Availability:
701
Brand:
AUTONICS

Not yet rated Write a review

Description

TC Series - one of the most cost effective temperature controlling solution with essential functions and improved performance - realizes ideal temperature controlling with newly developed PID control algorithm and 100ms high speed sampling. Especially, that both SSRP output and relay output are supported to realize effective and economical controlling; in addition, improved visibility and compact size is another feature of TC Series.

Main features
  • New low voltage models : 24VAC 50/60Hz, 24-48VDC
  • Advanced PID control algorithm and 100ms sampling speed
  • Built-in option to choose between relay or SSR outputs
  • Compact design and large display panels for better viewing
  • Dual digital display: TCN / Single digital display: TC
  • .

    Specifications

    Series TC4S TC4SP TC4Y TC4M TC4W TC4H TC4L
    Power supply AC power 100-240VAC 50/60Hz
    AC/DC power 24VAC 50/60HZ, 24-48VDC
    Allowable voltage range 90 to 110% of rated voltage
    Power consumption AC power Max. 5VA(100-240VAC 50/60Hz)
    AC/DC power Max. 5VA(24VAC 50/60Hz), Max. 3W(24-48VDC)
    Display method 7Segment(Red), Other display(Green, Yellow, Red) LED
    Character size W7xH15mm W7.4xH15mm W9.5xH20mm W9.5xH20mm W7.0xH14.6mm W11xH22mm
    Input type RTD DPt100Ω(Allowable line resistance max. 5Ω per a wire)
    Thermocouple K(CA), J(IC), L(IC)
    Display accuracy¶1 RTD, Thermocouple • At room temperature(23°C±5°C): (PV ±0.5% or ±1°C, select the higher one) ±1digit
    • Out of room temperature range: (PV ±0.5% or ±2°C, select the higher one) ±1digit
    ¶ In case of TC4SP Series, ±1°C will be added.
    Control output Relay 250VAC 3A 1 a
    SSR 12VDC ±2V 20mA Max.
    Sub output AL1, AL2 relay output : 250VAC 1A 1a(¶TC4SP, TC4Y have AL1 only.)
    Control method ON/OFF and P, PI, PD, PID control
    Hysteresis 1 to 100°C/°F(0.1 to 50.0°C/°F) variable
    Proportional band(P) 0.1 to 999.9°C/°F
    Integral time(l) 9999sec.
    Derivative time(D) 9999sec.
    Control period 0.5 to 120.0sec.
    Manual reset 0.0 to 100.0%
    Sampling period 100ms
    Dielectric strength AC power 2000VAC 50/60Hzfor 1min.(Between input terminal and power terminal)
    AC/DC power 1000VAC 50/60Hzfor 1min.(Between input terminal and power terminal)
    Vibration 0.75mm amplitude at frequency of 5 to 55Hz(for 1 mln.) In each of X, Y, Z directions for 2 hours
    Relay life cycle Mechanical OUT: Over 5,000,000 times, AL1/2: Over 5,000,000 times
    Electrical OUT: Over 200,000 times(250VAC 3A resistive load)
    AL1/2: Over 300,000 times(250VAC 1A resistive load)
    Insulation resistance Min. 100MΩ(at 500VDC megger)
    Noise resistance ±2kV R-phase, S-phase the square wave noise (pulse width: 1us) by the noise simulator
    Memory retention Approx. 10 years (when using non-volatile semiconductor memory type)
    Environ-ment -10 to 50°C, storage: -20 to 60°C
    35 to 85%RH, storage: 35 to 85%RH
    Insulation type Double insulation or reinforced insulation (mark: §, Dielectric strength between the measuring input part and the power part: AC power 2kV, AC/DC Power 1kV)
    Approval CE, UL (Except for AC/DC power type), RoHS (TC4S)
    Unit weight Approx. 141g Approx. 123g Approx. 174g Approx. 204g Approx. 194g Approx. 194g Approx. 254g
    Document download

    ¶ 1: Thermocouple L(IC) type, RTD Cu50Ω
    • At room temperature (23°C ±5°C): (PV ±0.5% or ±3°C, select the higher one) ±1digit
    • Out of room temperature range: (PV ±0.5% or ±4°C, select the higher one) ±1digit In case of TC4SP Series, ±1°C will be added.
    ¶ Environment resistance is rated at no freezing or condensation.