PID Control, 1/16 DIN, 4 digit Dual display, Relay & SSR Output, 2 Alarm Output, K/J/L/RTD Input, 100-240 VAC

$114.00

Model Number:
TCN4S-24R
Availability:
1026
Brand:
AUTONICS

Not yet rated Write a review

Description

TCN Series is economical temperature controllers having dual preset indicator display to increase user convenience. The series realizes ideal temperature controlling with newly developed PID control algorithm and 100ms high speed sampling; in addition, the series allows users to take advantage of economical controlling with SSRP and relay outputs. The TCN Series is also available in low voltage models for wider user options.

Main features
  • New low voltage models : 24VAC 50/60Hz, 24-48VDC
  • Advanced PID control algorithm and 100ms sampling speed
  • Built-in option to choose between relay or SSR outputs
  • Compact design and large display panels for better viewing
  • Dual digital display: TCN / Single digital display: TC
  • .

    Specifications

    Series TCN4S TCN4M TCN4H TCN4L
    Power AC power 100-240VAC 50/60Hz
    supply AC/DC power 24VAC 50/60Hz, 24-48VDC
    Allowable voltage range 90 to 110% of rated voltage
    Power consumption Max. 5VA(100-240VAC 50/60Hz, 24VAC 50/60Hz)
    Max. 3W(24-48VDC)
    Display method 7 Segment (PV: red, SV: green), Other display(green, red) LED
    Character PV(WxH) 7.0x15.0mm 9.5x20.0mm 7.0x14.6mm 11.0x22.0mm
    size SV(WxH) 5.0x9.5mm 7.5x15.0mm 6.0x12.0mm 7.0x14.0mm
    Input RTD DPt100Ω, Cu50Ω(Allowable line resistance max. 5Ω per a wire)
    type Thermocouple K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)
    Display RTD • At room temperature (23°C ±5°C): (PV ±0.5% or ±1°C, select the higher one) ±1digit
    • Out of room temperature range: (PV ±0.5% or ±2°C, select the higher one) ±1digit
    Display
    accuracy¶ 1
    Thermocouple
    Control output Relay 250VAC 3A 1 a
    SSR 12VDC ±2V 20mA Max.
    Alarm output AL1, AL2 Relay output : 250VAC 1A 1a
    Control method ON/OFF and P, PI, PD, PID control
    Hysteresis 1 to 100°C/°F (0.1 to 50.0°C/°F) variable
    Proportional band (P) 0.1 to 999.9°C/°F
    Integral time (I) 0 to 9999 sec.
    Derivative time (D) 0 to 9999 sec.
    Control period (T) 0.5 to 120.0 sec.
    Manual reset 0.0 to 100.0%
    Sampling period 100ms
    Dielectric strength AC Power 2,000VAC 50/60Hz 1min.(between input terminal and power terminal)
    AC/DC power 1,000VAC 50/60Hz 1min.(between input terminal and power terminal)
    Relay
    life cycle
    Mechanical OUT: Over 5,000,000 times, AL1/2: Over 5,000,000 times
    Electrical OUT: Over 200,000 times(250VAC 3A resistive load) AL1/2: Over 300,000 times(250VAC 1A resistive load)
    Vibration 0.75mm amplitude at frequency of 5 to 55Hz in each of x, Y, Z directions for 2 hours
    Insulation resistance Min. 100MΩ (at 500VDC megger)
    Noise resistance ±2kV R-phase, S-phase the square wave noise (pulse width: 1us) by the noise simulator
    Memory retention Approx. 10 years (when using non-volatile semiconductor memory type)
    Environment Ambient temperature -10 to 50°C, storage: -20 to 60°C
    Ambient humidity 35 to 85%RH, storage: 35 to 85%RH
    Insulation type Double insulation or reinforced insulation (mark: §, Dielectric strength between the measuring input part and the power part: AC power 2kV, AC/DC Power 1kV)
    Approval CE, UL
    Noise resistance Approx. 147g(Approx. 100g) Approx. 203g (Approx. 133g) Approx. 194g (Approx. 124g) Approx. 275g (Approx. 179g)
    Document download

    ¶ 1 :  At room temperature (23°C ±5°C)
    • Thermocouple C R, S type, below 200°C: (PV ±0.5% or ±3°C, select the higher one) ±1digit
    • Thermocouple R, S type, over 200°C: (PV ±0.5% or ±2°C, select the higher one) ±1digit
    • Thermocouple L(IC) type, RTD Cu50Ω: (PV ±0.5% or ±2°C, select the higher one) ±1digit
    Out of room temperature range
    • Thermocouple R, S type, below 200°C: (PV ±1.0% or ±6°C, select the higher one) ±1digit
    • Thermocouple R, S type, over 200°C: (PV ±0.5% or ±5°C, select the higher one ±1digit
    • RTD Cu50Ω: (PV ±0.5% or ±3°C, select the higher one) ±1digit
    ¶ 2: The weight is with packaging and the weight in parentheses is only unit weight.
    ¶ Environment resistance is rated at no freezing or condensation.