Board type temperature controller TB42 series increases user convenience by suitable panel composition for desired place and purpose. This series has high performances thru various functions including dual PID control function and time schedule function; in addition, the series realizes cost saving temperature controlling ever via reducing costs.

Main features
  • High quality and economical product
  • Convenient organization of panel to use
  • Dual PID control
  • Time reservation
  • .

    Specifications

    Model TB42-14R  TB42-14S  TB42-14C  TB42-14N
    Power supply 100-240VAC 50/60Hz ±10%
    Power consumption Approx. max. 5VA
    Display method 7 Segment(PV: green, SV: red) LED method
    Character size(WxH) 8x10mm
    Input type RTD DPt100Ω [Allowable line resistance is max. 5Ω per a wire]
    Thermocouple K(CA), J(IC) [Tolerance outer resistance is max. 100Ω]
    Control output Relay 250VAC 3A 1 a - - -
    SSR - 12VDC ±3V 30mA Max. - -
    Current - - DC4-20mA
    (load 600Ω Max.)
    -
    Transmission - - - DC4-20mA
    (load 600Ω Max.)
    Sub output • Event1 output : Relay output(250VAC 0.5A 1a)
    • Event2 output : OK monitoring display by LED

    Control method ON/OFF control(Hysteresis is adjustable), P, PI, PD, PIDF, PIDS
    Setting type Front push buttons
    Display accuracy F.S ± 0.3% or 3°C(Higher one)
    Hysteresis Adjustable 1 to 100°C(0.1 to 100.0°C) at ON / OFF control
    Proportional band(P) 0.0 to 100.0%
    Integral time(l) 0 to 3600sec.
    Derivative time(D) 0 to 3600sec.
    Control cycle(T) 1 to 120sec.
    Sampling period 0.5sec.
    Dielectric strength 2000VAC 50/60Hz for 1 minute(Between input and power terminal)
    Vibration 0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 2 hours
    Relay life cycl Vlaln output Mechanical: Min. 10,000,000, Electrical: Min. 100,000(250VAC 3A resistive load)
    Sub output Mechanical: Min. 20,000,000, Electrical: Min. 200,000(250VAC 0.5A resistive load)
    Insulation resistance Min. 100MΩ(at 500VDC megger)
    Noise strength ±2kV the square wave noise(pulse width : 1ms) by the noise simulator
    Memory protection Approx. 10 years(When using non-volatile semiconductor memory type)
    Environment Ambient temperature -10 to 50°C, storage: -20 to 60°C
    Ambient humidity 35 to 85%RH, storage: 35 to 85%RH
    Approval UL
    Unit weight Approx. 113.5g