Allowable Voltage Range |
90 ~ 110% of rated voltage
|
Power Consumption |
4 VA
|
Indication Method |
7 Segment Red LED Display (Red)
[Deviation signal (Green), unit display (Yellow)]
|
Display Method |
[PV &plusminus0.5 % or &plusminus1 °C Max.] rdg &plusminus 1 digit
|
Sampling Period |
500 MS
|
Control Method |
ON/OFF and proportional control (common use)
|
Hysteresis |
1 ~ 100 °C
|
Proportional Band |
0 ~ 100%
|
Offset Correction |
0 ~ 100%
|
Control Period |
1 ~ 120 sec.
|
Memory Protection |
Approx. 10 years (When using non-volatile semiconductor memory)
|
Insulation Resistance |
Min. 100MΩ (at 500 VDC)
|
Dielectric Strength |
2000 VAC 60 Hz for 1 minute (between all external terminal and case)
|
Noise Strength |
±2 kV R phase and S-phase (pulse width 1 µs)
|
Mechanical Relay Life Cycle |
Min. 10000000 times
|
Malfunction Relay Life Cycle |
Min. 10000000 times (250 VAC 3 A resistive load)
|
Vibration |
0.75mm amplitude at frequency of 10 to 55 Hz in each of X, Y, Z directions for 1 hours
|
Ambient Temperature |
-10 ~ 50 °C (at non-freezing status)
|
Storage Temperature |
-20 ~ 60 °C (at non-freezing status)
|
Ambient Humidity |
35 ~ 85%RH
|
Protection |
IP65
|
Dimensions |
DIN W72 x H36mm
|
Power Supply |
100 - 240 VAC
|
Control Output |
Relay 250VAC 3A 1c
|
Input Type |
RTD : Pt 100 Ω (DIN)
T.C (Thermocouples) : K (CA). J (IC)
|
Document download |
|