Series |
TAS |
Power supply |
100-240VAC 50/60Hz |
Allowable voltagerange |
90 to 110% of rated voltage |
Power consumption |
Max. 4VA |
Display method |
7Segment LED Display [Process value(PV) : Red, Setting value(SV) : Green] |
Size(WxH) |
DIN 48 mm x 48 mm |
Input type |
RTD |
DPt100Ω (allowable line resistance max. 5Ω per a wire) |
Thermocouples |
K(CA), J(IC) |
Control |
ON/OFF Control |
Hysteresis: 2°C fixed |
PID Control |
Control period: Relay output - 20 sec. /SSR drive output - 2 sec. |
Control
Output |
Relay |
250VAC 3A 1c |
SSR |
12VDC±2V 20mA Max. |
Functions |
PV deviation indicatable, Error indicatable |
Dielectric strength |
2,000VAC 50/60Hz for 1min. (between input terminal and power terminal) |
Vibration |
0.75mm amplitude at frequency of 5 to 55Hz (for 1 min.) in each X, Y, Z direction for 2 hours |
Relay life cycle |
Mechanical |
Min. 10,000,000 operations (18,000 operations/hr) |
Electrical |
Min. 100,000 operations (900 operations/hr) |
Insulation resistance |
Min. 100MΩ(at 500VDC megger) |
Noise resistance |
±2kV the square wave noise (pulse width: 1us) by the noise simulator |
Memory retention |
Approx. 10years(When using non-volatile semiconductor memory) |
Environment |
Ambient temperature |
-10 to 50°C, storage: -20 to 60°C |
Ambient humidity |
35 to 85%RH, storage: 35 to 85%RH |
Approval |
CE, UL |
Unit weight |
Approx. 112g |